Parameter
number
(DDE)
Parameter
name
Filter Value Description
2011-05-18 Page 3 of 5 FlowDDE database version V3.64
86 IO status &H40 analog jumper set (read only)1
86 IO status &H80 micro switch pressed (read only)1
106 Pressure sensor type delta-P 0..5" W.C.0
106 Pressure sensor type delta-P 0...10" W.C.1
106 Pressure sensor type absolute pressure 800-1200 mbar2
106 Pressure sensor type absolute pressure 800-1100 mbar3
106 Pressure sensor type delta-P -5...0 "W.C.4
106 Pressure sensor type delta-P -10...0 "W.C.5
106 Pressure sensor type delta-P -10...+10 "W.C.6
106 Pressure sensor type delta-P 0...1 PSI7
106 Pressure sensor type delta-P -1...0 PSI8
106 Pressure sensor type absolute pressure 0-10 bar10
114 Reset no reset0
114 Reset reset counter value (no mode change) or common reset1
114 Reset reset alarm2
114 Reset restart batch counter3
114 Reset reset counter value (counter off)4
114 Reset Reset module (soft reset)5
118 Alarm mode off0
118 Alarm mode alarm on absolute limits1
118 Alarm mode alarm on limits related to setpoint (response alarm)2
118 Alarm mode alarm when instrument powers-up (eg. after power-down)3
119 Alarm output mode no relais activity at alarm0
119 Alarm output mode relais pulses until reset1
119 Alarm output mode relais activated until reset2
120 Alarm setpoint mode no setpoint change at alarm0
120 Alarm setpoint mode new/safe setpoint at alarm enabled (set at par 121)1
125 Counter output mode no relais activity at batch limit0
125 Counter output mode relais pulses after reaching batch limit until reset1
125 Counter output mode relais activated after reaching batch limit until reset2
126 Counter setpoint mode setpoint change at batch limit disabled0
126 Counter setpoint mode setpoint change at batch limit enabled1
130 Counter mode off0
130 Counter mode counting upwards continuously1
130 Counter mode counting up to limit (batchcounter)2
147 Range select calibration ready/stop0
147 Range select run calibration until stopsensor 1/select range 11
147 Range select run calibration until stopsensor 2/select range 22
147 Range select run calibration until stopsensor 3/select range 33
147 Range select run calibration until stopsensor 4/select range 44
147 Range select run calibration and select range 55
147 Range select run calibration with automatic range selection9
147 Range select run until stopsensor 1 until 3 values between limit19
147 Range select run until stopsensor 2 until 3 values between limit29
147 Range select run until stopsensor 3 until 3 values between limit39
147 Range select run until stopsensor 4 until 3 values between limit49
147 Range select run and select range 5 until 3 values between limit59
147 Range select run with auto-select + 3 values between limit99
156 Reset alarm enable no reset possible0
156 Reset alarm enable reset: keyboard1
156 Reset alarm enable reset: external2
156 Reset alarm enable reset: keyboard or external3
156 Reset alarm enable reset: FLOW-BUS4
156 Reset alarm enable reset: FLOW-BUS or keyboard5
156 Reset alarm enable reset: FLOW-BUS or external6
156 Reset alarm enable reset: FLOW-BUS or keyboard or external7
156 Reset alarm enable reset: automatic8
156 Reset alarm enable reset: automatic or keyboard9
156 Reset alarm enable reset: automatic or external10
156 Reset alarm enable reset: automatic or keyboard or external11
156 Reset alarm enable reset: automatic or FLOW-BUS12
156 Reset alarm enable reset: automatic or FLOW-BUS or keyboard13
156 Reset alarm enable reset: automatic or FLOW-BUS or external14
156 Reset alarm enable reset: automatic or FLOW-BUS or keyboard or external15
157 Reset counter enable no reset possible0
157 Reset counter enable reset: keyboard1
157 Reset counter enable reset: external2
157 Reset counter enable reset: keyboard or external3
157 Reset counter enable reset: FLOW-BUS4
157 Reset counter enable reset: FLOW-BUS or keyboard5
157 Reset counter enable reset: FLOW-BUS or external6
157 Reset counter enable reset: FLOW-BUS or keyboard or external7
157 Reset counter enable reset: automatic8
157 Reset counter enable reset: automatic or keyboard9
157 Reset counter enable reset: automatic or external10
157 Reset counter enable reset: automatic or keyboard or external11
157 Reset counter enable reset: automatic or FLOW-BUS12
157 Reset counter enable reset: automatic or FLOW-BUS or keyboard13
157 Reset counter enable reset: automatic or FLOW-BUS or external14
157 Reset counter enable reset: automatic or FLOW-BUS or keyboard or external15
166 Controller features &H01 valve in normal position after startup0
166 Controller features &H01 valve in safe position after startup1
166 Controller features &H02 open from zero with PID output to valve0
166 Controller features &H02 open from zero with ramp output to valve1