Parameter values table
Parameter
number
(DDE)
Parameter
name
Filter Value Description
2011-05-18 Page 1 of 5 FlowDDE database version V3.64
6 Arbitrage temporary busmaster1
6 Arbitrage always busmaster2
6 Arbitrage automatic busmaster3
6 Arbitrage auto busmaster and auto bus optimalization (fast token ring)67
12 Control mode setpoint = BUS setpoint0
12 Control mode setpoint = analog input1
12 Control mode setpoint = master output(FLOW-BUS) * slave factor(FLOW-BUS)2
12 Control mode close valve3
12 Control mode controller idle (no reaction on changes in sensor signal)4
12 Control mode testmode enable (select subject with par 70)5
12 Control mode tuningmode enable (select subtject with par 79)6
12 Control mode setpoint = 100%7
12 Control mode purge valve (fully open)8
12 Control mode calibration mode enable (select subject with par 58)9
12 Control mode setpoint = master output(analog in) * slave factor(FLOW-BUS)10
12 Control mode setpoint = keyboard OR FLOW-BUS setpoint11
12 Control mode setpoint = 0%12
12 Control mode setpoint = master output(FLOW-BUS) * slave factor(analog in)13
12 Control mode (FPP) Range select mode14
12 Control mode (FPP) Manual start sensor select, automatic end sensor15
12 Control mode (FPP) Automatic start sensor select, manual end sensor16
12 Control mode (FPP) Automatic start and end sensor17
12 Control mode setpoint = RS232 setpoint18
12 Control mode RS232 broadcast mode19
12 Control mode valve stearing (valve = setpoint)20
12 Control mode analog valve stearing (valve = analog setpoint)21
12 Control mode valve safe state22
22 Sensor type pressure (controller)0
22 Sensor type liquid volume (controller)1
22 Sensor type liquid/gas mass (controller)2
22 Sensor type gas volume (controller)3
22 Sensor type other sensor type (controller)4
22 Sensor type pressure (sensor)128
22 Sensor type liquid volume (sensor)129
22 Sensor type liquid/gas mass (sensor)130
22 Sensor type gas volume (sensor)131
22 Sensor type other sensor type (sensor)132
28 Alarm info &H01 no error message in alarm error status register0
28 Alarm info &H01 at least 1 error message in alarm error status register1
28 Alarm info &H02 no warning message in alarm warning status register0
28 Alarm info &H02 at least 1 warning message in alarm warning status register1
28 Alarm info &H04 no minimum alarm message (measure>minimum limit)0
28 Alarm info &H04 minimum alarm message for measured signal1
28 Alarm info &H08 no maximum alarm message (measure<maximum limit)0
28 Alarm info &H08 maximum alarm message for measured signal1
28 Alarm info &H10 batch counter has not reached its limit0
28 Alarm info &H10 batch counter has reached its limit1
28 Alarm info &H20 response O.K. (setpoint-measure within limit)0
28 Alarm info &H20 response alarm message: setpoint-measure is too high1
28 Alarm info &H40 master output signal O.K. (or not used)0
28 Alarm info &H40 master output signal not received: check master instrument1
28 Alarm info &H80 hardware O.K.0
28 Alarm info &H80 hardware error message: check your hardware1
44 Operation mode T/A OFF0
44 Operation mode T/A A: MAX & RESP AUTO; T: UP TO LIMIT1
44 Operation mode T/A A: MIN & RESP AUTO; T: UP AND REPEAT2
44 Operation mode T/A A: MAX & RESP; T: DOWN FROM LIMIT3
44 Operation mode T/A A: MIN & RESP; T: DOWN AND REPEAT4
44 Operation mode T/A A: MAXIMUM ALARM; T: ALWAYS UP5
44 Operation mode T/A A: MINIMUM ALARM6
44 Operation mode T/A A: RESPONSE ALARM7
53 Analog mode &H3F 0...5 Vdc operation0
53 Analog mode &H3F 0...10 Vdc operation1
53 Analog mode &H3F 0...20 mA operation2
53 Analog mode &H3F 4...20 mA operation3
53 Analog mode &H3F 15...20 mA operation4
53 Analog mode &H40 Analog input enabled0
53 Analog mode &H40 Analog input disabled1
53 Analog mode &H80 Analog output enabled0
53 Analog mode &H80 Analog output disabled1
58 Calibration mode idle: no action0
58 Calibration mode adc self calibration1
58 Calibration mode dmfc2
58 Calibration mode dmfc3
58 Calibration mode dmfc4
58 Calibration mode dmfc5
58 Calibration mode dmfc6
58 Calibration mode dmfc7
58 Calibration mode dmfc8
58 Calibration mode customer zero9