12.1.2 LEDindicationsmode(MBC3only)
forthisstate Led Indication
NetworkstatusLED(NET)
Notpowered/Not
online
Off Deviceisnotonline
ThedevicehasnotbeencompletedtheDup_MAC_IDtestyet.
Thedevicemaynotbepowered,lookatmodulestatusLED
Nonetworkpowerpresent
LinkOK,Online,
Connected
On
green
Deviceisonlineandhasconnectionsintheestablishedstate
Foragroup2deviceitmeansthatthedeviceisallocatedtoamaster.
Online,Not
connected
Flashing
green
0.5secon
0.5secoff
Thedeviceisonlinebuthasnoconnectionsintheestablishedstate.
ThedevicehaspassedtheDup_MAC_IDtest,isonlinebuthasno
establishedconnectionstoothernodes
Foragroup2device
itmeansthatthedeviceisnotallocatedtoamaster.
ConnectionTime‐
out
Flashing
red
0.5secon
0.5secoff
OneormoreI/Oconnectionsareintimed‐outstate.
CriticallinkFailure On
red
Failedcommunicationdevice.Thedevicehasdetectedanerrorthathas
rendereditincapableofcommunicatingonthenetwork.(DuplicateMACIDor
busoff)
ModulestatusLED(MOD)
Nopower Off Thereisnopowerappliedtothedevice
Deviceoperational On
green
Thedeviceisoperatinginnormalcondition.
DeviceinStandby
(Thedeviceneeds
commissioning)
Flashing
green
0.5secon
0.5secoff
Thedeviceneedscommissioningduetoconfigurationmissing,incompleteor
incorrect.Thedevicemaybeinthestandbystate.
Unrecoverablefault On
red
Thedevicehasanunrecoverablefault,mayneedreplacing.
Deviceselftesting Flashing
red/green
0.5secon
0.5secoff
Thedeviceisinselftest.
ModuleandstatusLED’ssequenceatpower‐up
NetworkLED(NET) off
ModuleLED(MOD)
green 0.25sec
ModuleLED(MOD)
red 0.25sec
ModuleLED(MOD)
green
NetworkLED(NET)
green 0.25sec
NetworkLED(NET)
red 0.25sec
NetworkLED(NET) off
Moreinformationcanbefoundinthemanual“917023Operationalinstructionsdigitalinstruments