9.4 VIARS232:OTHERPROGRAMS
Itisalso possibletoreadandor changestation address orbaud rate by meansofany program viaRS232 usingthe
COM‐portofyourPCon38.4KBaud.ThiscanbeachievedusingtheFLOW‐BUSprotocol.
Thefollowingtablegivestheparametersinproc125which
maybeused:
Parameter Type R/W Initmode Description
9 LONG R/W Softinit Baudrate forfieldbus interface
10 CHR R/W Softinit Fieldbus stationaddress/MACID
MoredetailedinformationabouttheRS232protocol(document9.17.027)canbefoundat:
http://www.bronkhorst.com/en/downloads/instruction_manuals/
9.5 VIAMICRO‐SWITCHANDLEDSONTOPOFINSTRUMENT
Withthemicro‐switchontopoftheinstrumentitispossibletochangeandreadoutthesettingsforMAC‐IDandbaud
rate.TheLED’swillindicatethetensof theaddress with greenflashesandtheunits with red flashes.Forbaud rate
indicationbothLED’swillflash.
Seedocument9.17.023foradetaileddescription
Thisdocumentcanbefoundat:
http://www.bronkhorst.com/en/downloads/instruction_manuals/