Page25DeviceNetinterface 9.17.026
4.3 ANALOGSENSOROBJECT
4.3.1 Sensorvalue
SeeSetpointattributeofSinglestagecontrollerabove.
4.3.2 Alarmenable
AttributeAlarmenableofAnalogSensorobjectislinkedtopropar97;3(Alarmmode).
FLOWBUS Devicenet
Alarmmode Alarmenable
proc97;par3 obj0x31,attr8
ALRM_OFF
(ALRM_RESPONSE)
(ALRM_POWERFAILURE)
0(off)
ALRM_MINMAX 1(on)
When 0 is written to Alarm enable attribute, the internal alarm mode is always set to ALRM_OFF. The modes
ALRM_RESPONSEandALRM_POWERFAILUREcanbesetbyRS232,notbyDeviceNet.
Moreinformationcanbefoundinthemanual“917023Operationalinstructionsdigitalinstruments
Thisdocumentcanbefoundat:
http://www.bronkhorst.com/en/downloads/instruction_manuals/
4.3.3 AlarmTripPoints
Alarm_Trip_Point_Lowattributeislinkedtopropar97/2(Min.limit). Validrangeis[0,32000].
Alarm_Trip_Point_Highattributeislinkedtopropar97/1(Max.limit). Validrangeis[0,32000].
Avalueoutsidethevalidrangeisroundedtothenearestvaluewithintherange.NotethattheTripPointvaluesare
dependent
ontheselecteddatatypes/units.
Forthemaximumvaluethefollowingmappingisused:
FLOWBUS DeviceNet
Maxlimit AlarmTripPointHigh
proc97;par1 obj0x31,attr17
0(off) 32000
1 0
32000 31999
4.3.4 Gascalibrationobjectinstance
IndicateswhichGasCalibrationobjectinstanceisactiveforthisobject.Thevalueofthisattributeisequalto
(fluidnumer+1).Value0(disabled)isnotsupported.
4.4 ANALOGACTUATOROBJECTINSTANCE
4.4.1 Actuatorvalue
Thefollowingsdataunitsaresupported:
0x1001(counts): 0=valveclosed,32767=valvefullyopen
0x1007(percent): 0=valveclosed,100=valvefullyopen
Thefollowingdatatypesaresupported: 0xC3(int) 0xCA(real)