Bronkhorst Multibus Bedienungsanleitung Seite 25

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 50
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 24
BRONKHORST®
Page 25 Operational instructions for digital multibus instruments 9.17.023
5.11 V
ALVE SAFE STATE
Unsigned char
0…255
RW
N
301
115/31
The controller module will go to a safe state in the following situations:
If bus communication is lost and control mode = 0 (DeviceNet and PROFIBUS only)
if initreset = 73
if control mode = 22 (new safe state control mode)
In fail safe state the green LED will be blinking (0.1 s on, 2 sec off).
The valve will react to the fail safe state according to the table below.
Decimal value
Description
0
Deactivate valve (0mA)
1
Activate valve (max current)
2
Close valve
3
Open valve
4
Hold valve in current position
5
Hold valve at safe value
If Initreset = 73 the fail safe state mode will always be “hold valve in current position”
“Hold valve at safe value” can only be used with DeviceNet instruments.
Seitenansicht 24
1 2 ... 20 21 22 23 24 25 26 27 28 29 30 ... 49 50

Kommentare zu diesen Handbüchern

Keine Kommentare