Instruction manual PROFIBUS DP® slave interface for digital multibus Mass Flow / Pressure instruments Doc. no.: 9.17.025Q Date: 15-10-2014 ATTENTION
BRONKHORST® 2.5 SPUR LINES WITH PROFIBUS DP (Also known as stubs or branches) In table 5 the maximum spur capacitance is set out to the baud rate.
BRONKHORST® 2.6 NETWORK TERMINATION A PROFIBUS DP network segment is based on an RS485 standard and requires two (2) and only two (2), termination r
BRONKHORST® 3 CONFIGURATION 3.1 GSD-FILE Each type PROFIBUS DP instrument should have its own GSD-file with instrument specifications to tell the
BRONKHORST® 3.2 CONFIGURATION SOFTWARE In this manual we use as an example the software tool from Hilscher G.m.b.H. The configuration tools offer vi
BRONKHORST® 3.3 ADD SLAVE TO PROFIBUS DP In your master configuration software select: [Insert][slave]. Select [Bronkhorst meter/controller] and ev
BRONKHORST® 3.4 SLAVE CONFIGURATION SETTINGS Bronkhorst PROFIBUS DP instruments offer many available modules/parameters for operation of the instr
BRONKHORST® 3.5 SLAVE PARAMETER SETTINGS If you want to give your instrument specific values for certain variables at start-up you can do this by m
BRONKHORST® 4 SLAVE ADDRESSING 4.1 GENERAL When you have installed your Bronkhorst meter/controller PROFIBUS DP slave and made right settings for s
BRONKHORST® Re-address action can be checked using the option ‘Live list’. This gives an overview of all masters and slaves connected to a PROFIBUS se
BRONKHORST® Start-up FlowFix.exe and select COM-port. Then the configuration screen will appear. Enter slave station address and press [OK]. Chang
BRONKHORST® Disclaimer Even though care has been taken in the preparation and publication of the contents of this manual, we do not assume legal or
BRONKHORST® 5 DOWNLOAD TO MASTER When slave has been installed and all settings are done, everything has to be downloaded to the master. Point to a
BRONKHORST® 6 TEST COMMUNICATION Some master configuration tool programs offer facilities to read input I/O and write output I/O data. In this monit
BRONKHORST® 7 SAFE STATE If PROFIBUS communication problems occur, so when instrument is not in data exchange mode, the instrument forces the val
BRONKHORST® 8 TROUBLESHOOTING 8.1 LED INDICATION Led Time Indication Green off Continuously Power-off or program not running on Continuous
BRONKHORST® 8.2 TROUBLESHOOTING HINTS AND TIPS PROFIBUS problems No Communication • Check power supply and cabling. • Check bus termination. At
BRONKHORST® 9 SERVICE For current information on Bronkhorst and service addresses please visit our website: http://www.bronkhorst.com Do you hav
BRONKHORST® Table of contents 1 GENERAL PRODUCT INFORMATION ...
BRONKHORST® 1 GENERAL PRODUCT INFORMATION 1.1 INTRODUCTION This manual will explain how to install a Bronkhorst1 instrument to your PROFIBUS DP
BRONKHORST® 1.3 REFERENCES TO OTHER APPLICABLE DOCUMENTS Manuals and guides for digital instruments are modular. General instructions give informat
BRONKHORST® 1.4 SHORT FORM START-UP All necessary settings for this module are already performed at Bronkhorst. To follow next steps carefully is th
BRONKHORST® 1.5 OPERATING PRINCIPLES PROFIBUS DP is a 2-wire industrial data communication standard (Field bus) which allows automation components
BRONKHORST® 2 FIELD BUS INSTALLATION 2.1 GENERAL The following installation guidelines only apply to data transfer using copper cables (RS 485) t
BRONKHORST® 2.3 PROFIBUS DP CABLES PROFIBUS cables are shielded twisted-pair copper cables which differ from each other in the typ