4.4.4 Diagnostics (08)
The following sub-functions are supported
Clear Counters and Diagnostics Register
Return Bus Communication Error Count
Return Bus Exception Error Count
Return Slave Message Count
Return Slave No Response Count
Return Slave NAK Count (always 0)
Return Slave Busy Count (always 0)
Return Bus Character Overrun Count
Warning: the maximum message size for the Return Query Data sub function is 100 bytes at 9600 baud
(200 bytes at 19200 baud and 400 bytes at 38400 baud). When this size is exceeded, corrupted
responses may be received.
Possible exception responses
of not-supported sub-function
in case of an incorrect value for the data field
in case of writing illegal value to register
4.4.5 Report Slave ID (17)
The Slave ID field in the response is a string with the same contents as FlowDDE parameter 1 (ident number + version
nr/serial nr). The Run Indicator Status field in this message will indicate ON when the device is in normal operating
mode (FB_NORMAL).
Possible exception responses
in case of an internal error
Page 18 Modbus interface 9.17.035