Bronkhorst FLOW-BUS interface Bedienungsanleitung Seite 11

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 26
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 10
BRONKHORST®
2 FIELDBUSINSTALLATION
2.1 GENERAL
FLOW‐BUSis a 3‐wire,RS485‐basedfield buscommunicationsystemfor parameter valueexchangebetweendigital
Bronkhorstproducts.Inthissystemeachinstrument/deviceisequippedwithamicro‐controllerforitsowndedicated
task but also for exchanging parameter value information with other instruments /devices connected to the sam
e
FLOW‐BUSsystem.
FLOW‐BUSsystemsmayhaveaminimumof2andamaximumof126connections.Themaximumlengthfordatelines
between the first and the last connection may be up to approx. 600 meters. Longer distances are only possible in
combination with special bus‐repeater m
odules. Each instrument/device connection T‐part (stub) must be kept as
shortaspossible(maximumcablelength0.5meter).
Thebaudrateusedtotransportmessagesis187500baudor400000*baud.
FLOW‐BUSisamulti‐masternetworkwithatoken‐ringarchitecture.
*MBC3typeinstrumentshaveanadditionalbaudrateavailableof400000baud.
Page11
FLOW‐BUSinterface9.17.024